ISA Interchange

Welcome to the official blog of the International Society of Automation (ISA).

This blog covers numerous topics on industrial automation such as operations & management, continuous & batch processing, connectivity, manufacturing & machine control, and Industry 4.0.

The material and information contained on this website is for general information purposes only. ISA blog posts may be authored by ISA staff and guest authors from the automation community. Views and opinions expressed by a guest author are solely their own, and do not necessarily represent those of ISA. Posts made by guest authors have been subject to peer review.

All Posts

How Optimal Measurement Location Maximizes Sensor Sensitivity and Signal-To-Noise Ratio

 

The following tip is from the ISA book by Greg McMillan and Hunter Vegas titled 101 Tips for a Successful Automation Career, inspired by the ISA Mentor Program. This is Tip #67, and was written by Greg.

 

I became sensitized to the importance of measurement location when I found the easiest way to keep a pH electrode from fouling was to install it in a pipe with a flow velocity of 5 to 7 fps, preventing the usual 100X deterioration in the speed of response that resulted from just a few millimeters of coating. The higher velocity also made the electrode much faster-responding when clean. The conventional wisdom of putting an electrode into a vessel was proven wrong on several counts. The velocity in even the most highly agitated vessels is only 1 fps, resulting in a slow response and the need to remove the electrode more frequently. Furthermore, removing an electrode from a vessel in service is more problematic than removing it from a recirculation line that can be isolated.

I also found that pH electrodes installed too close to the outlet of a static mixer were too noisy. Moving the electrodes downstream 25 pipe diameters made a world of difference. The increase in loop deadtime was only 1.5 sec from the additional transportation delay (9 feet of 4-inch pipe at 6 fps). The decrease in noise allowed me to use a smaller filter time so that the actual total loop deadtime was less.

The same principle applies to thermowells, although the effect is less dramatic. Higher velocities decrease the fouling rate and decrease the measurement lag, the result of an increase in the heat transfer coefficient. (The annular clearance (air gap) between the sensor and the inside diameter of the thermowell has a bigger effect than velocity.) The thermowell should also be about 25 pipe diameters downstream of a heat exchanger to allow for mixing of the flows from the tubes.

 

Bubbles in liquid streams and droplets in gas streams cause noise when they hit a sensor. Bubbles from air, oxygen, and carbon dioxide spargers in bioreactors and chemical reactors can cause dissolved oxygen and pH signals to become noisy. Droplets of water at a desuperheater outlet cause a noisy temperature measurement. Ammonia bubbles at a static mixer outlet cause a noisy pH measurement.

The tip of an electrode or thermowell should be near the pipe centerline because the temperature and composition vary over the cross section of the pipe. For highly viscous fluids, the error is pronounced. I found that the temperature measurement in extruder outlets and the pH measurement in static mixer outlets with a sulfuric acid reagent are particularly sensitive to the depth of insertion of the sensor tip due to the effects of the high viscosity of polymers and of 98% sulfuric acid.

Differential head meters and vortex meters should be located where the velocity profile is uniform, the flow is turbulent, and there is a single phase - or wherever the piping designer tells you (just kidding).

Concept: The sensor location should provide sufficient residence time and mixing to ensure a single phase and a uniform mixture. The location should minimize the volume between the point of injection and the sensor to minimize delay. For differential head and vortex meters, a consistent velocity profile is required. Most importantly, the location must be sensitive to changes in both directions of the process.

Details: Maximize the detection of changes in the process from disturbances and setpoint changes. For composition, pH, and temperature choose the location that shows the largest change in both directions for a positive and negative change in the ratio of the manipulated flow to the feed flow, realizing that there are cross-sectional and longitudinal temperature and concentration profiles in pipes and equipment. For distillation columns, the best location for the thermowell is the tray with the largest change in temperature for an increase or decrease in the reflux to distillate ratio or steam to distillate ratio. A temperature or pH sensor and an analyzer sample tip should be near the center of a pipe and should extend well past equipment walls. A series of temperature sensors across a fluidized bed at several longitudinal distances is often necessary, with averaging and signal selection to get a representative measurement and prevent hot spots.

The insertion length of a thermowell should be more than five times the diameter of the thermowell to minimize thermal conduction-induced errors from heat conduction along the thermowell wall between the tip and the process connection. To prevent vibration failure from wake frequencies in pipes, calculations should be run with the program supplied by the manufacturer on the allowable maximum length. A location with good mixing and a single phase will minimize fluctuations in measured temperature and concentration and the disruption caused by bubbles or solids in liquids and liquid droplets in gases hitting temperature or pH sensors or getting into sample lines for analyzers or into impulse lines for pressure and level measurements. Pressure probes in high-velocity gas streams and furnaces must be designed to minimize momentum and vacuum effects. Sensors and sample probe tips should not be installed on pump suctions and should be downstream of strainers. Minimize sensor deadtime and lag by reducing transportation delays and increasing velocities.

The transportation delay in a pipe or sample line is the volume divided by the flow rate or the distance divided by the velocity. The lag time of temperature and pH sensors decreases with velocity by an increase in the heat transfer and mass transfer coefficient, respectively. Fouling also decreases with velocity.

 

Watch-outs: Material volumes behind baffles or near the surface or bottom of an agitated vessel or at the outlet of inline equipment may not be well-mixed. Packed and fluidized bed equipment may have uneven composition and temperature distribution from flow channeling. Programs for vibration analysis may only be looking at thermowell failure and will not predict RTD failure. The use of calcium hydroxide (lime) or magnesium hydroxide as a reagent may seem cost-effective until you consider the cost of poor control and solids going downstream.

Exceptions: The best location may not be accessible or maintainable due to height or obstructions.

Insight: The best measurement location maximizes the sensor sensitivity and maximizes the signal-to-noise ratio and minimizes deadtime.

Rule of Thumb: Find a location that is sensitive to changes in the process, where the fluid has a uniform mixture and a single phase, and where sensor lag and transportation delay are minimized.

 

About the Author

Hunter Vegas, P.E., holds a B.S.E.E. degree from Tulane University and an M.B.A. from Wake Forest University. His job titles have included instrument engineer, production engineer, instrumentation group leader, principal automation engineer, and unit production manager. In 2001, he joined Avid Solutions, Inc., as an engineering manager and lead project engineer, where he works today. Hunter has executed nearly 2,000 instrumentation and control projects over his career, with budgets ranging from a few thousand to millions of dollars. He is proficient in field instrumentation sizing and selection, safety interlock design, electrical design, advanced control strategy, and numerous control system hardware and software platforms.

 

Greg McMillan
Greg McMillan
Gregory K. McMillan, CAP, is a retired Senior Fellow from Solutia/Monsanto where he worked in engineering technology on process control improvement. Greg was also an affiliate professor for Washington University in Saint Louis. Greg is an ISA Fellow and received the ISA Kermit Fischer Environmental Award for pH control in 1991, the Control magazine Engineer of the Year award for the process industry in 1994, was inducted into the Control magazine Process Automation Hall of Fame in 2001, was honored by InTech magazine in 2003 as one of the most influential innovators in automation, and received the ISA Life Achievement Award in 2010. Greg is the author of numerous books on process control, including "New Directions in Bioprocess Modeling and Control Second Edition 2020" and "Advanced pH Measurement and Control Fourth Edition 2023." Greg has been the monthly "Control Talk" columnist for Control magazine since 2002. Greg has recently retired as a part-time modeling and control consultant in Technology for Process Simulation for Emerson Automation Solutions specializing in the use of the digital twin for exploring new opportunities. Greg received the ISA Mentoring Excellence Award in 2020 and the ISA Standards Achievement Award in 2023.

Related Posts

3 Ways Industry 4.0 Can Upgrade Industrial Water Treatment Methods

Industrial water treatment methods must evolve to remain relevant and efficient. Many decision-makers hav...
Emily Newton Mar 12, 2024 7:38:26 PM

ISA Business Academy: A Mini-MBA For Automation Industry Leaders

The ISA Business Academy is a 10-week fully digital program beginning 28 March for both current and aspir...
Ashley Ragan Mar 11, 2024 10:08:24 AM

How Automation Is Transforming the Recycling Industry

Modern recycling industry professionals are increasingly interested in how automation could boost their o...
Ellie Gabel Mar 8, 2024 8:00:00 AM