  • rajesh dwivedi

    I have one query regarding cable laying order in vertical cable tray stack.

    As per API RP 552 IN VERTICAL STACK of cable trays, signal wiring should be on top tray and high voltage feeder tray on bottom most but as per IEEE 525/ 422 this shall be in reverse order i.e. high voltage cables would be in top tray and signal cables are in bottom most tray. (in both the cases distance between trays are same but only order is changed)

    kindly suggest which standard shall be followed and why.

    • ISA Staff

      Rajesh,
      Thanks for your question. In this case ISA Standards don’t cover the issue you brought up. You would do better to contact either API or IEEE directly.
      Sorry we couldn’t be of more help.